2217895
Wilo - Stratos Maxo 25/0,5-10 PN10-R7 Glandless Circulator Pump - 230V - Single Phase - 10 Bar. - 180mmPremium smart-pump Wilo-Stratos MAXO-R7
High efficiency in line glandless pump with EC motor and electronic power adjustment. Can be utilised for Cold water, heating water and water/glycol mixtures. Energy efficiency index (EEI) between 0.17 and 0.19 depending on pump type.
Control modes:
Permanent, automatic power adjustment to system requirements without setpoint specification Wilo - Dynamic Adapt plus (factory setting). Up to 20% energy savings compared to dp-v control mode., Constant temperature (T-const.), Constant differential temperature (dT-const.), Needs-based volume flow optimisation of the feeder pump through connectivity and communication between multiple pumps (Multi-Flow Adaptation)., Constant volume flow (Q-const.), Differential pressure control (dp-c) to a remote point in the pipe network (index circuit evaluator), Constant differential pressure (dp-c), Variable differential pressure (dp-v) with the option to set the nominal duty point, Constant speed (n-const.), and User-defined PID control.
Product Functions:
Heat quantity measurement, Cooling quantity measurement, Pump automatically deactivates when no flow is detected (No-Flow Stop), Switchover between heating and cooling mode (automatic, external or manual) (automatic, possible with Stratos MAXO temperature sensor), Adjustable volume flow limiter using the Q-Limit function (Qmin. and Qmax.), Operating modes of twin-head pumps: Efficiency-optimised parallel operation for dp-c and dp-v, main and standby operation, Ability to save and restore configured pump settings (3 restoration points), Fault and warning messages shown in plain text with advice on resolving the issue, Pump venting function for automatic venting of the rotor chamber, Automatic setback operation (possible with Stratos MAXO temperature sensor), Automatic deblocking function and integrated full motor protection, and Dry-running detection.
Display:
- Control mode
- Setpoint
- Volume flow
- Temperature (possible with Stratos MAXO temperature sensor)
- Power consumption
- Electric consumption
- Active influences (e.g. STOP, No-Flow Stop)
Version:
- 2 configurable analogue inputs: 0š10 V, 2š10 V, 0š20 mA, 4š20 mA and commercially available PT1000; +24 V DC power supply
- 2 configurable digital inputs (Ext. OFF, Ext. Min, Ext. Max, heating/cooling, manual override (uncoupled from building automation), operation lock (key lock and remote operation configuration protection))
- 2 configurable signal relays for run signals and fault messages
- Slot for Wilo-CIF modules with interfaces for building automation BA (optional accessories: CIF modules Modbus RTU, Modbus TCP, BACnet MS/TP, BACnet IP, LON, PLR, CANopen)
- Wilo - Net as a Wilo - system bus for communication between Wilo - products, e.g. Multi-Flow Adaptation; twin-head pump operation and Wilo-Smart Gateway
- Automatic emergency operation with definable pump speed for exceptional circumstances, e.g. bus communication or sensor value malfunction
- Graphic colour display (4.3 inches) with one-button manual operation
- Use the Wilo-Assistant app to read and set operating data and šamong other thingsš set up a commissioning protocol through the Bluetooth interface (no further accessories required)
- Integrated dual pump management (twin-head pumps are prewired) when using 2 single pumps as twin-head pump unit (connection via Wilo - Net)
- Cable break detection when using an analogue signal (in connection with 2š10 V or 4š20 mA)
- Outdoor Installation manual with weather protection possible in accordance with the Installation manual and operating instructions
- Pre-set date and time
- Thermal insulation shell for heating applications
Scope of delivery
- Pump
- Optimised Wilo-Connector the same for all sizes
- 2x threaded cable connection M16 x 1.5
- 2x gaskets
- Thermal insulation shell
- Concise Installation manual and operating instructions
Optional accessories:
- ClimaForm Cold insulation to avoid the formation of condensate
- CIF module: Modbus TCP, Modbus RTU, BACnet IP, BACnet MS/TP, LON, PLR, CANopen
- PT 1000 (B) pipe contact sensor (for domestic Hot water)
- PT 1000 (AA) sensor for Installation manual in immersion well
- Differential pressure sensor
- Smart Gateway
- Stratos MAXO temperature sensor (can be retrofitted for recording and displaying the fluid temperature and using the temperature-controlled control modes T-const., dT-const.)
In stock
Free Standard Delivery
-
2217900
Wilo - Stratos Maxo 30/0,5-10 PN10-R7 Glandless Circulator Pump - 230V - Single Phase - 10 Bar. - 180mmHigh efficiency in line glandless pump with EC motor and electronic power adjustment. Can be utilised for Cold water, heating water and water/glycol mixtures. Energy efficiency index (EEI) between 0.17 and 0.19 depending on pump type.
Control modes:
Permanent, automatic power adjustment to system requirements without setpoint specification Wilo - Dynamic Adapt plus (factory setting). Up to 20% energy savings compared to dp-v control mode., Constant temperature (T-const.), Constant differential temperature (dT-const.), Needs-based volume flow optimisation of the feeder pump through connectivity and communication between multiple pumps (Multi-Flow Adaptation)., Constant volume flow (Q-const.), Differential pressure control (dp-c) to a remote point in the pipe network (index circuit evaluator), Constant differential pressure (dp-c), Variable differential pressure (dp-v) with the option to set the nominal duty point, Constant speed (n-const.), and User-defined PID control.
Product Functions:
Heat quantity measurement, Cooling quantity measurement, Pump automatically deactivates when no flow is detected (No-Flow Stop), Switchover between heating and cooling mode (automatic, external or manual) (automatic, possible with Stratos MAXO temperature sensor), Adjustable volume flow limiter using the Q-Limit function (Qmin. and Qmax.), Operating modes of twin-head pumps: Efficiency-optimised parallel operation for dp-c and dp-v, main and standby operation, Ability to save and restore configured pump settings (3 restoration points), Fault and warning messages shown in plain text with advice on resolving the issue, Pump venting function for automatic venting of the rotor chamber, Automatic setback operation (possible with Stratos MAXO temperature sensor), Automatic deblocking function and integrated full motor protection, and Dry-running detection.
Display:
- Control mode
- Setpoint
- Volume flow
- Temperature (possible with Stratos MAXO temperature sensor)
- Power consumption
- Electric consumption
- Active influences (e.g. STOP, No-Flow Stop)
Version:
- 2 configurable analogue inputs: 0š10 V, 2š10 V, 0š20 mA, 4š20 mA and commercially available PT1000; +24 V DC power supply
- 2 configurable digital inputs (Ext. OFF, Ext. Min, Ext. Max, heating/cooling, manual override (uncoupled from building automation), operation lock (key lock and remote operation configuration protection))
- 2 configurable signal relays for run signals and fault messages
- Slot for Wilo-CIF modules with interfaces for building automation BA (optional accessories: CIF modules Modbus RTU, Modbus TCP, BACnet MS/TP, BACnet IP, LON, PLR, CANopen)
- Wilo - Net as a Wilo - system bus for communication between Wilo - products, e.g. Multi-Flow Adaptation; twin-head pump operation and Wilo-Smart Gateway
- Automatic emergency operation with definable pump speed for exceptional circumstances, e.g. bus communication or sensor value malfunction
- Graphic colour display (4.3 inches) with one-button manual operation
- Use the Wilo-Assistant app to read and set operating data and šamong other thingsš set up a commissioning protocol through the Bluetooth interface (no further accessories required)
- Integrated dual pump management (twin-head pumps are prewired) when using 2 single pumps as twin-head pump unit (connection via Wilo - Net)
- Cable break detection when using an analogue signal (in connection with 2š10 V or 4š20 mA)
- Outdoor Installation manual with weather protection possible in accordance with the Installation manual and operating instructions
- Pre-set date and time
- Thermal insulation shell for heating applications
Scope of delivery
- Pump
- Optimised Wilo-Connector the same for all sizes
- 2x threaded cable connection M16 x 1.5
- 2x gaskets
- Thermal insulation shell
- Concise Installation manual and operating instructions
Optional accessories:
- ClimaForm Cold insulation to avoid the formation of condensate
- CIF module: Modbus TCP, Modbus RTU, BACnet IP, BACnet MS/TP, LON, PLR, CANopen
- PT 1000 (B) pipe contact sensor (for domestic Hot water)
- PT 1000 (AA) sensor for Installation manual in immersion well
- Differential pressure sensor
- Smart Gateway
- Stratos MAXO temperature sensor (can be retrofitted for recording and displaying the fluid temperature and using the temperature-controlled control modes T-const., dT-const.)
In stock
Free Standard Delivery
-
2217945
Wilo - Stratos maxo 32/0,5-8 R7 Glandless Circulator Pump - 230V - Single Phase - 10 Bar. - 220mmPremium smart central heating pump Wilo-Stratos MAXO-R7
High efficiency in line glandless pump with EC motor and electronic power adjustment. Can be utilised for Cold water, heating water and water/glycol mixtures. Energy efficiency index (EEI) between 𢧠0.17 and 𢧠0.19 depending on pump type.
Control modes:
Permanent, automatic power adjustment to system requirements without setpoint specification Wilo - Dynamic Adapt plus (factory setting). Up to 20% energy savings compared to dp-v control mode., Constant temperature (T-const.), Constant differential temperature (dT-const.), Needs-based volume flow optimisation of the feeder pump through connectivity and communication between multiple pumps (Multi-Flow Adaptation)., Constant volume flow (Q-const.), Differential pressure control (dp-c) to a remote point in the pipe network (index circuit evaluator), Constant differential pressure (dp-c), Variable differential pressure (dp-v) with the option to set the nominal duty point, Constant speed (n-const.), and User-defined PID control.
Product Functions:
Heat quantity measurement, Cooling quantity measurement, Pump automatically deactivates when no flow is detected (No-Flow Stop), Switchover between heating and cooling mode (automatic, external or manual) (automatic, possible with Stratos MAXO temperature sensor), Adjustable volume flow limiter using the Q-Limit function (Qmin. and Qmax.), Operating modes of twin-head pumps: Efficiency-optimised parallel operation for dp-c and dp-v, main and standby operation, Ability to save and restore configured pump settings (3 restoration points), Fault and warning messages shown in plain text with advice on resolving the issue, Pump venting function for automatic venting of the rotor chamber, Automatic setback operation (possible with Stratos MAXO temperature sensor), Automatic deblocking function and integrated full motor protection, and Dry-running detection.
Display:
- Control mode
- Setpoint
- Volume flow
- Temperature (possible with Stratos MAXO temperature sensor)
- Power consumption
- Electric consumption
- Active influences (e.g. STOP, No-Flow Stop)
Version:
- 2 configurable analogue inputs: 0š10 V, 2š10 V, 0š20 mA, 4š20 mA and commercially available PT1000; +24 V DC power supply
- 2 configurable digital inputs (Ext. OFF, Ext. Min, Ext. Max, heating/cooling, manual override (uncoupled from building automation), operation lock (key lock and remote operation configuration protection))
- 2 configurable signal relays for run signals and fault messages
- Slot for Wilo-CIF modules with interfaces for building automation BA (optional accessories: CIF modules Modbus RTU, Modbus TCP, BACnet MS/TP, BACnet IP, LON, PLR, CANopen)
- Wilo - Net as a Wilo - system bus for communication between Wilo - products, e.g. Multi-Flow Adaptation; twin-head pump operation and Wilo-Smart Gateway
- Automatic emergency operation with definable pump speed for exceptional circumstances, e.g. bus communication or sensor value malfunction
- Graphic colour display (4.3 inches) with one-button manual operation
- Use the Wilo-Assistant app to read and set operating data and šamong other thingsš set up a commissioning protocol through the Bluetooth interface (no further accessories required)
- Integrated dual pump management (twin-head pumps are prewired) when using 2 single pumps as twin-head pump unit (connection via Wilo - Net)
- Cable break detection when using an analogue signal (in connection with 2š10 V or 4š20 mA)
- Outdoor Installation manual with weather protection possible in accordance with the Installation manual and operating instructions
- Pre-set date and time
- Thermal insulation shell for heating applications
Scope of delivery
- Pump
- Optimised Wilo-Connector the same for all sizes
- 2x threaded cable connection M16 x 1.5
- 2x gaskets
- Thermal insulation shell
- Concise Installation manual and operating instructions
Optional accessories:
- ClimaForm Cold insulation to avoid the formation of condensate
- CIF module: Modbus TCP, Modbus RTU, BACnet IP, BACnet MS/TP, LON, PLR, CANopen
- PT 1000 (B) pipe contact sensor (for domestic Hot water)
- PT 1000 (AA) sensor for Installation manual in immersion well
- Differential pressure sensor
- Smart Gateway
- Stratos MAXO temperature sensor (can be retrofitted for recording and displaying the fluid temperature and using the temperature-controlled control modes T-const., dT-const.)
In stock
Free Standard Delivery
-
2217904
Wilo - Stratos Maxo-D 30/0,5-10 PN10-R7 Twin Head Glandless Circulator Pump - 230V - Single Phase - 10 Bar. - 180mmPremium smart central heating pump Wilo-Stratos MAXO-D-R7
High-efficiency in line glandless twin-head pump with EC motor and electronic power adjustment. Can be utilised for Cold water, heating water and water/glycol mixtures. Energy efficiency index (EEI) between 𢧠0.17 and 𢧠0.19 depending on pump type.
Control modes:
Permanent, automatic power adjustment to system requirements without setpoint specification Wilo - Dynamic Adapt plus (factory setting). Up to 20% energy savings compared to dp-v control mode., Constant temperature (T-const.), Constant differential temperature (dT-const.), Needs-based volume flow optimisation of the feeder pump through connectivity and communication between multiple pumps (Multi-Flow Adaptation)., Constant volume flow (Q-const.), Differential pressure control (dp-c) to a remote point in the pipe network (index circuit evaluator), Constant differential pressure (dp-c), Variable differential pressure (dp-v) with the option to set the nominal duty point, Constant speed (n-const.), and User-defined PID control.
Product Functions:
Heat quantity measurement, Cooling quantity measurement, Pump automatically deactivates when no flow is detected (No-Flow Stop), Switchover between heating and cooling mode (automatic, external or manual) (automatic, possible with Stratos MAXO temperature sensor), Adjustable volume flow limiter using the Q-Limit function (Qmin. and Qmax.), Operating modes of twin-head pumps: Efficiency-optimised parallel operation for dp-c and dp-v, main and standby operation, Ability to save and restore configured pump settings (3 restoration points), Fault and warning messages shown in plain text with advice on resolving the issue, Pump venting function for automatic venting of the rotor chamber, Automatic setback operation (possible with Stratos MAXO temperature sensor), Automatic deblocking function and integrated full motor protection, and Dry-running detection.
Display:
- Control mode
- Setpoint
- Volume flow
- Temperature (possible with Stratos MAXO temperature sensor)
- Power consumption
- Electric consumption
- Active influences (e.g. STOP, No-Flow Stop)
Version:
- 2 configurable analogue inputs: 0š10 V, 2š10 V, 0š20 mA, 4š20 mA and commercially available PT1000; +24 V DC power supply
- 2 configurable digital inputs (Ext. OFF, Ext. Min, Ext. Max, heating/cooling, manual override (uncoupled from building automation), operation lock (key lock and remote operation configuration protection))
- 2 configurable signal relays for run signals and fault messages
- Slot for Wilo-CIF modules with interfaces for building automation BA (optional accessories: CIF modules Modbus RTU, Modbus TCP, BACnet MS/TP, BACnet IP, LON, PLR, CANopen)
- Wilo - Net as a Wilo - system bus for communication between Wilo - products, e.g. Multi-Flow Adaptation; twin-head pump operation and Wilo-Smart Gateway
- Automatic emergency operation with definable pump speed for exceptional circumstances, e.g. bus communication or sensor value malfunction
- Graphic colour display (4.3 inches) with one-button manual operation
- Use the Wilo-Assistant app to read and set operating data and šamong other thingsš set up a commissioning protocol through the Bluetooth interface (no further accessories required)
- Integrated dual pump management (twin-head pumps are prewired) when using 2 single pumps as twin-head pump unit (connection via Wilo - Net)
- Cable break detection when using an analogue signal (in connection with 2š10 V or 4š20 mA)
- Outdoor Installation manual with weather protection possible in accordance with the Installation manual and operating instructions
- Pre-set date and time
Scope of delivery
- Pump
- 2x optimised Wilo-Connector, appropriate for all sizes
- 4x threaded cable gland, M16 x 1.5
- 2x gaskets
- Concise Installation manual and operating instructions
Optional accessories:
- CIF module: Modbus TCP, Modbus RTU, BACnet IP, BACnet MS/TP, LON, PLR, CANopen
- PT 1000 (B) pipe contact sensor (for domestic Hot water)
- PT 1000 (AA) sensor for Installation manual in immersion well
- Differential pressure sensor
- Smart Gateway
- Stratos MAXO temperature sensor (can be retrofitted for recording and displaying the fluid temperature and using the temperature-controlled control modes T-const., dT-const.)
In stock
Free Standard Delivery
-
2217972
Wilo - Stratos Maxo 100/0,5-12 PN10-R7 Glandless Circulator Pump - 230V - Single Phase - 10 Bar. - 360mmPremium smart central heating pump Wilo-Stratos MAXO-R7
High efficiency in line glandless pump with EC motor and electronic power adjustment. Can be utilised for Cold water, heating water and water/glycol mixtures. Energy efficiency index (EEI) between 𢧠0.17 and 𢧠0.19 depending on pump type.
Control modes:
Permanent, automatic power adjustment to system requirements without setpoint specification Wilo - Dynamic Adapt plus (factory setting). Up to 20% energy savings compared to dp-v control mode., Constant temperature (T-const.), Constant differential temperature (dT-const.), Needs-based volume flow optimisation of the feeder pump through connectivity and communication between multiple pumps (Multi-Flow Adaptation)., Constant volume flow (Q-const.), Differential pressure control (dp-c) to a remote point in the pipe network (index circuit evaluator), Constant differential pressure (dp-c), Variable differential pressure (dp-v) with the option to set the nominal duty point, Constant speed (n-const.), and User-defined PID control.
Product Functions:
Heat quantity measurement, Cooling quantity measurement, Pump automatically deactivates when no flow is detected (No-Flow Stop), Switchover between heating and cooling mode (automatic, external or manual) (automatic, possible with Stratos MAXO temperature sensor), Adjustable volume flow limiter using the Q-Limit function (Qmin. and Qmax.), Operating modes of twin-head pumps: Efficiency-optimised parallel operation for dp-c and dp-v, main and standby operation, Ability to save and restore configured pump settings (3 restoration points), Fault and warning messages shown in plain text with advice on resolving the issue, Pump venting function for automatic venting of the rotor chamber, Automatic setback operation (possible with Stratos MAXO temperature sensor), Automatic deblocking function and integrated full motor protection, and Dry-running detection.
Display:
- Control mode
- Setpoint
- Volume flow
- Temperature (possible with Stratos MAXO temperature sensor)
- Power consumption
- Electric consumption
- Active influences (e.g. STOP, No-Flow Stop)
Version:
- 2 configurable analogue inputs: 0š10 V, 2š10 V, 0š20 mA, 4š20 mA and commercially available PT1000; +24 V DC power supply
- 2 configurable digital inputs (Ext. OFF, Ext. Min, Ext. Max, heating/cooling, manual override (uncoupled from building automation), operation lock (key lock and remote operation configuration protection))
- 2 configurable signal relays for run signals and fault messages
- Slot for Wilo-CIF modules with interfaces for building automation BA (optional accessories: CIF modules Modbus RTU, Modbus TCP, BACnet MS/TP, BACnet IP, LON, PLR, CANopen)
- Wilo - Net as a Wilo - system bus for communication between Wilo - products, e.g. Multi-Flow Adaptation; twin-head pump operation and Wilo-Smart Gateway
- Automatic emergency operation with definable pump speed for exceptional circumstances, e.g. bus communication or sensor value malfunction
- Graphic colour display (4.3 inches) with one-button manual operation
- Use the Wilo-Assistant app to read and set operating data and šamong other thingsš set up a commissioning protocol through the Bluetooth interface (no further accessories required)
- Integrated dual pump management (twin-head pumps are prewired) when using 2 single pumps as twin-head pump unit (connection via Wilo - Net)
- Cable break detection when using an analogue signal (in connection with 2š10 V or 4š20 mA)
- Outdoor Installation manual with weather protection possible in accordance with the Installation manual and operating instructions
- Pre-set date and time
- Thermal insulation shell for heating applications
Scope of delivery
- Pump
- Optimised Wilo-Connector the same for all sizes
- 2x threaded cable connection M16 x 1.5
- 2x gaskets
- Thermal insulation shell
- Concise Installation manual and operating instructions
Optional accessories:
- ClimaForm Cold insulation to avoid the formation of condensate
- CIF module: Modbus TCP, Modbus RTU, BACnet IP, BACnet MS/TP, LON, PLR, CANopen
- PT 1000 (B) pipe contact sensor (for domestic Hot water)
- PT 1000 (AA) sensor for Installation manual in immersion well
- Differential pressure sensor
- Smart Gateway
- Stratos MAXO temperature sensor (can be retrofitted for recording and displaying the fluid temperature and using the temperature-controlled control modes T-const., dT-const.)
In stock
Free Standard Delivery